Data-center heat meets the community pool
A pool is one of the few neighbourhood loads that can take data-center heat at 30 °C directly, with a plate heat exchanger and no heat pump. Pick a climate, a data center, its cooling architecture and a pool, and watch the month-by-month balance: how much of the pool’s heat the data center covers, how much of the data center’s heat the pool absorbs, and what the pool owner stops paying for.
What to look for
Pool demand peaks in January and collapses in summer; data-center heat is flat all year. In cold climates a 0.5 MW edge site keeps a 50 m pool warm through winter; a hyperscale campus barely notices it. Use Fill the data center to see how many pools of a given type one site could carry in its peak month.
1 · Climate
2 · Data center
2.0 MW IT load3 · Cooling type
4 · Pool
5 · Number of pools
Assumptions
Year-round heat balance · Boston, MA
Pool heat demand
3,205 MWh/yr
2,564 kWh per m² of surface
Demand met by DC heat
100 %
Covered in every month
Share of DC heat absorbed
24 %
of 13,140 MWh/yr recoverable
Peak load, one pool
685 kW
January monthly average; sizes the heat exchanger
What the pool owner saves (heat actually delivered)
vs gas heater
$169k/yr
84 % efficiency at $1.30/therm
vs heat pump
$136k/yr
801 MWh electricity at COP 4
CO₂ avoided vs gas
691 t/yr
EPA factor 53 kg per MMBtu
Value of the heat
$0.053/kWh
ceiling an offtaker could pay before connection costs
Temperature match
Direct use: supply water is above the pool by at least 3 K, so a plate heat exchanger moves the heat with no heat pump.